T500 HART -> PROFIbus PA
Gateway for allowing HART instruments to connect to PROFIbus PA networks.
General description:
The T500 is DIN rail module for interfacing HART instruments to a PROFIbus PA network. Both current
sinking and current sourcing HART transmitters are supported.
The T500 is a complete transmitter module. It allows interfacing up to 4 HART instruments. It generates a measured variable including a status variable indicating the quality of the measurement.
The HART instruments must be preconfigured to multidrop and be given addresses in the
range 1 - 16. The T500 will automatically establish connection to the HART transmitter at power-up. When the
HART instrument is detected, key parameters are read from the instrument and will be visible on the PROFIbus side. The T500
will read Unit codes, sensor limits and range values from the HART transmitters. These values
will be available on PROFIbus from a Master Class two using DP V1.
T500 includes a HART master in order to communicate with a HART instrument. The module reads the variables from the instrument
and converts this to a dynamic variable on PA. Four AI Function Blocks are supported, one for each instrument. By reconfiguring
the T500 it is possible to read four dynamic variables from one instrument. The latter
application will require use of a configuration tool or the T500 can be ordered preconfigured from FINT.
The HART instrument may be powered through the T500. T500 has a separate 24 V input for this.
The HART support is limited to the Universal commands. The T500 does not support configuration of the HART transmitter through PROFIbus.
The T500generates one measured variable including a status variable indicating the quality of the
measurement for each HART transmitter. The Primary Variable (PV) will be continuously read and updated. Any HART communication
problem will be reported in the PA Diagnostics message.
The T500 supports alarm flagging. The user can configure four alarm levels using a standard configuration tool.
The T500 supports low-pass filtering. The user can configure the damping value using a standard configuration tool.
Other Function blocks can be added on request. The HART slaves are supposed to work in multidrop mode.
The HART Universal command parameters are available from the PA side.
The T500 supports the PROFIbus PA profile 3.0.
No special programming is required to set up the device.
Applications:
The T500 is intended for integration of existing HART instruments into PROFIbus PA network. It is intended for system integrators that are building PROFIbus based systems, and manufacturers of measurement devices who want to offer PROFIbus PA capabilities on their HART instruments.